Product functions are mainly divided into two categories: temperature function and humidity function;
Temperature Function:
1. Automatic Mode Identification:
The system automatically recognizes the working mode based on the start temperature/stop temperature.
Start Temperature > Stop Temperature = Cooling Mode 'C'; Start Temperature < Stop Temperature = Heating Mode 'H'.
2. Cooling Mode:
When the detected temperature is ≥ start temperature, the relay is activated, the red light turns on, and the cooling equipment starts working.
When the detected temperature is ≤ stop temperature, the relay is turned off, the red light goes out, and the cooling equipment stops working.
3. Heating Mode:
When the detected temperature is ≤ start temperature, the relay is turned on, the red light turns on, and the heating equipment starts working.
When the detected temperature is ≥ stop temperature, the relay is turned off, the red light goes out, and the heating equipment stops working.
4. OFE (-10.0 ~ 10.0) Temperature Correction Function:
As the system operates over time, deviations may occur. Use this function to correct the actual temperature = measured temperature + calibration value.
How to Set Start/Stop Temperature:
1. On the running interface, press and hold the "TM+" button for more than 3 seconds to enter the start temperature setting interface. You can change parameters using the TM+ and TM- buttons. After finishing, wait 6 seconds for automatic exit and save.
2. On the running interface, press and hold the "TM-" button for more than 3 seconds to enter the stop temperature setting interface. You can change parameters using the TM+ and TM- buttons. After finishing, wait 6 seconds for automatic exit and save.
Humidity Functions:
1. Automatic Mode Identification:
The system automatically recognizes the working mode based on the start humidity/stop humidity.
Start Humidity > Stop Humidity = Dehumidification Mode 'd'; Start Humidity < Stop Humidity = Humidification Mode 'E'.
2. Dehumidification Mode:
When the detected humidity is ≥ start humidity, the relay is activated, the green light turns on, and the dehumidification equipment starts working.
When the detected humidity is ≤ stop humidity, the relay is turned off, the green light goes out, and the dehumidification equipment stops working.
3. Humidification Mode:
When the detected humidity is ≤ start humidity, the relay is activated, the green light turns on, and the humidification device starts working.
When the detected humidity is ≥ stop humidity, the relay is turned off, the green light goes out, and the humidification device stops working.
4. RH Humidity Correction Function (-10.0 ~ 10.0):
As the system operates over time, deviations may occur. Use this function to correct the actual humidity = measured humidity + calibration value.
How to Set Start/Stop Humidity:
1. On the running interface, press and hold the "RH+" button for more than 3 seconds to enter the start humidity setting interface. You can change parameters using the RH+ and RH- buttons. After finishing, wait 6 seconds for automatic exit and save.
2. On the running interface, press and hold the "RH-" button for more than 3 seconds to enter the stop humidity setting interface. You can change parameters using the RH+ and RH- buttons. After finishing, wait 6 seconds for automatic exit and save.
-
브랜드: